- 01The KPM CBA01 measures the dynamic characteristics of high-voltage circuit breakers on site: closing and opening time of up to 12 contacts, asynchronism between poles and breaks, bounce time and number of bounces, contact travel, clearance, overtravel and rebound, average speed, and speed at the instant contacts touch or separate.It also runs close-open, open-close and rated operating sequences (O-CO, CO-CO, O-CO-CO), low-voltage operation tests, and timing of contactors and relays. With a travel sensor fitted it records current-time, travel-time and speed-time curves.
- 02
- 03From top left: the earth terminal and communication port; four groups of timing inputs (A1 B1 C1 to A4 B4 C4); the close, open and common control terminals with their fuse; the travel sensor input, external trigger input and stored-energy (spring charging) output; and the mains power socket and switches. On the right are the fast-connection socket, the printer and the colour touchscreen.Front panel: 1 earth and communication, 2 timing inputs, 3 control, 4-6 sensor, trigger and stored energy, 7 power, 8 fast connection, 9 printer, 10 touchscreen.
- 04The analyzer, an accessory box, timing leads and extension leads, a 250 mm and a 25 mm linear sensor, an angle (rotary) sensor, a connecting rod, magnetic joint and magnetic movable frame, clip and holder, a three-clip shorting lead, the close/open control lead (red, green and black), an external trigger lead, a six-core sensor cable, earth lead, power lead, USB lead and five spare 10 A/250 V fuses.Sensors and mounting accessories supplied with the analyzer.
- 05Connect the moving contact of every pole together and to the analyzer's earth terminal, then earth it reliably. Connect the fixed contact of each pole to the A, B and C inputs of a timing group. For breakers with several breaks per pole, use the further groups (2, 3, 4).Group 4 (A4, B4, C4) is the group used when a travel sensor is installed.Timing leads: fixed contacts to A, B and C; moving contacts joined and earthed.
- 06
- 07With the built-in supply, connect the analyzer's Close, Open and Common terminals to the breaker's closing coil, opening coil and common terminal. Common is the positive output; Close and Open are negative.With an external trigger, do not connect Close, Open and Common. Instead connect the external trigger input in parallel with the breaker's coil, so it sees the coil voltage as the start signal.Close, Open and Common terminals for the built-in coil supply.
- 08Use the built-in supply where it can drive the breaker's coils, because it lets you set the exact voltage. If the built-in supply cannot meet the breaker's requirements, select External Trigger and operate the breaker from its own supply.Never wire the built-in supply and the external trigger at the same time.Choose Internal Power or External Trigger before the test.
- 09
- 10It is a 10-pin connector that carries the A, B, C and earth timing signals and the close and open control lines in one plug. With the matching lead, wiring a breaker takes a single connection. Do not use the fast connection and the separate panel sockets at the same time.Fast connection socket: timing, earth and control in one plug.
- 11
- 12
- 13A 25 mm linear sensor, a 250 mm linear sensor and an angle (rotary) sensor are supplied as standard. 300 mm and 1000 mm linear sensors are available as options for breakers with longer travel. Choose the one that suits the breaker's travel and the space around its mechanism, then select the same sensor in the test settings.Select the sensor that is fitted.
- 14Mount it on a rotating shaft of the mechanism with the magnetic base or the clamp bracket and the connecting link. Because it measures angle, the analyzer needs a ratio to convert degrees into millimetres of contact travel.Set the ratio K1 to 1.00 mm/° and run a close or open test to read the angle C for the open clearance. Then the correct ratio is K2 = S ÷ C, where S is the breaker's standard open clearance. Enter K2 and test again.Angle sensor mounted on the magnetic base
- 15
- 16Open the cover of the arc chamber, pass the extension rod into the chamber and screw it into the moving contact's threaded hole. Couple the other end to the sensor so the sensor moves in the same direction as the moving contact, and fix the sensor to the chamber.Connect the sensor to the travel input. Wire the timing leads as usual: moving contacts to earth, fixed contacts to A, B and C.Oil breaker: extension rod, sensor and timing leads.
- 17With the breaker open, fix the sensor to the support frame under the breaker and adjust the spring so the probe just touches the moving contact. Connect the probe lead to the External Trigger input, and the timing leads as for an oil breaker.Used this way, A1 records when the contacts separate and the External Trigger input records when the moving contact reaches its fixed point, so the analyzer can show the moving contact's operating time.Vacuum breaker: sensor under the breaker, timing leads to each pole.
- 18Remove the glass window of the operating rod housing, fix the sensor mounting plate into the screw holes, set the linear sensor in position, and adjust it so it slides freely up and down with the rod. Wire the timing leads as for the other breaker types.SF6 breaker: linear sensor on the operating rod.
- 19Tap Close Test and check each setting: breaker type, sampling time, average speed definition, instant speed definition (not for vacuum breakers), sensor, and power type and output voltage. Then tap Run.An open test is set up the same way from Open Test.Close test settings: breaker type, test time, speed definitions, sensor and voltage.
- 20
- 21
- 22
- 23
- 24
- 25Tap Low V. Test. Set the starting voltage and the percentage, then use the arrows to step the voltage and percentage by the gaps you set. Tap Close or Open to operate the breaker at each level and find the lowest voltage at which it still operates reliably.Low-voltage test: step voltage and percentage, then Close or Open.
- 26
- 27
- 28A table with closing (or opening) time, bounce time and number of bounces for every break, plus asynchronism between phases and breaks. With a sensor fitted it also shows travel, clearance, overtravel, average speed and instant speed.From this screen you can save the result, print it, or view the curve.Result screen: times per break, asynchronism, travel and speed.
- 29
- 30
- 31
- 32
- 33Connect the analyzer to the PC with the USB lead. On the analyzer, open Setting and tap Connect. In the software, click Connect, then Upload to receive all stored results. Choose a result from the list on the left to see its curves and values. Read shows the last uploaded data again.PC software: uploaded travel curve and timing.
- 34
- 35
- 36Earth the analyzer and the breaker under test before connecting anything else. Use only the supplied power lead. Never connect the built-in coil supply and the external trigger together, or the fast connection together with the panel sockets.Follow your site's isolation and earthing rules, and keep clear of the breaker mechanism during operations.
- 37
- 38
- 39Timing: up to 12 contacts, 0 to 6 s range, 0.01 ms resolution, 0.1 ms accuracy. Travel: 25 mm and 250 mm sensors as standard, 300 mm and 1000 mm optional; 0.001 mm resolution, 1 mm accuracy. Speed: 0 to 20 m/s. Built-in DC supply 0 to 265 V, up to 20 A. Mains 220 V AC ±10%, 50 Hz, under 60 W. Operating temperature 0 to 40 °C, humidity up to 90% RH. Size 460 × 340 × 200 mm, weight 10 kg.
- 40
- 41