- 01A CT PT analyzer is a portable instrument that tests current transformers (CTs) and voltage transformers (PTs/VTs) without a high-voltage source or a reference transformer. It injects a controlled low voltage into the CT secondary, measures the response, and calculates the excitation curve, knee point, turns ratio, ratio and phase error, winding resistance, polarity and burden.It then compares every result with the accuracy class you selected and gives a pass or fail. The KPM CTA C+ does all of this in one 14 kg case with a built-in computer, replacing a bench of separate sources, meters and a variac.The KPM CT PT Analyzer: colour-coded test terminals on the left, display and keypad on the front panel.
- 02On a CT it measures the excitation curve and knee point, turns ratio, ratio and phase error, polarity, winding resistance and secondary burden. It also gives the 5% and 10% error curves for protection CTs, ALF, FS, remanence (Kr), transient parameters (Ts, Ktd) and, where the nameplate is missing, a deduced nameplate. On a PT it measures turns ratio, ratio and phase angle error, polarity, burden and winding resistance.Only two quantities are measured directly, voltage and current, to high precision. Everything else is calculated from them, which is why the accuracy of those two measurements decides the quality of every result.
- 03You can test CTs the conventional way with a variac, an ammeter, a voltmeter and a reference CT, and for decades everyone did. It works. It costs time, a lot of bench equipment, a reference CT that itself needs calibrating, and results that depend on someone reading analogue meters late in the day.A CT PT analyzer does not do anything that was impossible before. It turns half a day of careful work into minutes, removes the reference CT from the chain and produces a report nobody has to retype. If you test two CTs a year, it is not worth the money. If you test two hundred, it clearly is.
- 04A full CT analysis (excitation curve, knee point, turns ratio, ratio and phase error at several current points and two burdens, winding resistance and polarity) runs as one automated sequence once the leads are connected and the parameters entered.The slow part is now the connecting, and on a multi-core CT, shorting the cores not under test. In practice a bay's worth of CTs can be tested and reported before lunch, work that takes two days with a manual method.
- 05Four groups use one. Testing and commissioning companies need speed and a report the client accepts. Utilities and transmission companies test at commissioning and during maintenance. Instrument transformer manufacturers use one for routine and type tests.Industrial plants with their own high-voltage yards, such as steel, cement, refineries and captive power plants, use one because a metering CT error quietly costs money on every bill until someone checks.
- 06Inside is a programmable voltage and current source, isolated from the mains, controlled by a digital signal processor (DSP). The DSP sets the output, samples the response on two precision measurement inputs, and passes the data to a built-in computer that does the calculations and stores the results, typically a thousand or more test records.The source is the simple part. The measurement side is where the cost goes: resolving voltage and current to about 0.1% is what makes every derived figure trustworthy.Inside a CT PT analyzer: a mains-isolated source controlled by a DSP, two measurement inputs and a built-in computer.
- 07It works backwards. The analyzer drives the CT secondary with a controlled low voltage and measures the voltage induced at the primary, the reverse of how the CT works in service. Because a CT steps current down, it steps voltage up by the same ratio, so a modest secondary voltage produces a measurable primary voltage.This is what makes portable CT testing possible. It is also why the CT primary must be disconnected from the line before testing: any connection to the system brings in noise that corrupts the small signals being measured.CT analysis, ratio and polarity test: power output and CT secondary input on the secondary winding, CT primary input on the primary.
- 08A CT is driven from its secondary. A voltage transformer is driven from its primary, through an excitation module connected in series with the analyzer output, and the secondary is measured. The test list is shorter: turns ratio, ratio and phase angle error, polarity, secondary burden and winding resistance.One practical point affects accuracy: if the PT secondary circuit is left open during a ratio test, burden and excitation losses are excluded from the result. Leaving it connected gives the more realistic answerPT testing: the analyzer drives the PT primary through the excitation test module connected in series with its output.
- 09The knee point is where a current transformer stops behaving like a transformer. Below it, the core magnetises easily and the secondary faithfully reproduces the primary current. Above it, the core saturates, the excitation current rises sharply, and current that should reach the relay is used to magnetise the iron instead.A CT PT analyzer finds it by measuring the excitation curve up into saturation and applying the knee point definition of the selected standard. It matters because a protection CT must stay below its knee during the worst fault it will ever carry.
- 10Because the standards define the knee point differently. Under IEC 60044-1 it is the point where a 10% rise in voltage causes a 50% rise in excitation current, both in RMS. IEC 60044-6 uses the same rule but on peak values. IEEE C57.13 uses a tangent construction instead: the point where the curve's tangent reaches 45° (ANSI 45) or 30° (ANSI 30).Same CT, same measured curve, different knee point numbers. A knee point result means nothing unless the standard is stated with it.
- 11The excitation curve plots secondary voltage against the excitation current needed to produce it, measured point by point into saturation. A long straight rise with a sharp, late bend means a core with plenty of margin. An early, gentle bend means a core that will saturate under fault conditions.Comparing a curve with the same CT's curve from an earlier test is one of the most useful things you can do. A curve that has shifted points to a core or winding problem long before the CT fails outright.
- 12When a CT saturates, the secondary current collapses away from its true value and the waveform distorts into narrow spikes. A meter reads wrong. A distance relay sees an impedance that is not there, a differential relay sees a difference current that does not exist, and an overcurrent relay may not pick up at all.Saturation gives no warning in service; the relay simply makes a wrong decision. A CT PT analyzer predicts it in advance from the excitation curve, the knee point, the ALF and the error curves, before the CT is put into service.
- 13By testing at a low frequency, a method the standards permit. Core flux depends on voltage divided by frequency, so the voltage needed to reach a given flux falls in proportion to the test frequency. Lower the frequency far enough and a knee point that would need tens of kilovolts at 50 Hz is reached with a few hundred volts.The instrument then scales the result back to rated frequency. This is how the KPM CTA C+ measures knee points up to 80 kV from a 360 V output, stays light enough to carry, and never puts a dangerous voltage on the CT terminals.
- 14Remanence is magnetisation the iron core keeps after the current that caused it has gone. A CT that has carried a heavy fault, or had DC injected during a winding resistance test, keeps some flux and starts its next duty from there instead of from zero. It then saturates earlier than its nameplate suggests.A CT PT analyzer reports the remanence factor (Kr) from the measured hysteresis loop. For protection classes such as 5PR and 10PR, the standards cap remanence, typically at 10%.
- 15Because leftover magnetisation shifts the results. A core still carrying remanent flux from a fault, or from the DC of a winding resistance test, gives an excitation curve and ratio error that describe a magnetised core, not the CT itself.That is why a CT PT analyzer runs degaussing as its own step before the measurements that matter. It is easy to forget in a manual test and impossible to forget in an automated one.
- 16Burden is the load on the CT secondary: relays, meters and, above all, the wiring between them, stated in VA at a given power factor. A CT's accuracy is only defined at a stated burden. Too much burden needs more excitation current, which never reaches the meter, so the ratio error grows.That is why a proper test measures the real secondary loop instead of trusting the nameplate. A CT PT analyzer calculates ratio and phase error at both the rated burden and the burden actually connected, in one test.CT secondary burden test: the analyzer measures the real secondary loop of relays, meters and wiring.
- 17The class on the nameplate holds only under stated conditions, and site conditions are often different. Three things break it. The burden may be too high, because long cable runs add resistance and circuits grow over the years. The current may be too low, because a CT sized for a load that never came runs at a few percent of rating, where errors are larger. Or the CT may have degraded.All three are invisible from the ground, and all three show up in a CT PT analyzer test.
- 18Ratio error is how far the actual current ratio departs from the marked ratio, in percent. Phase error is the angle between primary and secondary current, in minutes; it matters wherever power or energy is calculated.Limits tighten with class and loosen at low current. A class 0.5 CT may have 0.5% ratio error at 100% of rated current but 1.5% at 5%; class 0.1 allows 0.1% and 0.4% at the same points. Protection classes are looser at rated current, 1% for 5P and 3% for 10P, because they are judged at fault current.
- 19They show, for one protection CT, how much secondary burden it can carry at each multiple of rated current before its composite error passes 5% or 10%. Burden and fault current trade off: more burden means less fault current before the limit is crossed. The 5% curve suits 5P CTs and the 10% curve suits 10P CTs.Protection engineers ask for them because they answer the key design question: with the relays and cable run actually installed, will this CT still tell the truth at maximum fault current? A CT PT analyzer plots both curves from the measured data, without injecting fault current.
- 20FS protects meters. A metering CT should saturate early in a fault, so the huge primary current is not passed through to the instruments. FS is the multiple of rated current at which the metering core's composite error reaches 10%, and a lower number is safer: FS5 saturates sooner than FS10.The CT PT analyzer checks that the measured FS is no greater than the rated FS. A metering core that saturates later than its nameplate claims lets fault current through to the meters.
- 21ALF is the multiple of rated current up to which a protection CT keeps its composite error within limits. The 20 in 5P20 means twenty times rated current. Here a higher number is better, and the CT PT analyzer checks that the measured ALF is at least the rated ALF, at the rated burden and at the actual burden.FS and ALF point in opposite directions, which is why one core cannot serve metering and protection well, and why CTs have separate cores for each.
- 22They are CT accuracy classes. Metering classes (0.1, 0.2, 0.2S, 0.5, 0.5S, 1, 3, 5) give the allowed ratio error in percent at rated current; the S means accuracy is also guaranteed down to 1% of rated current. Protection classes carry a P: 5P and 10P allow 5% and 10% composite error, and the number after it is the ALF, so 5P20 means 5% error up to twenty times rated current.An R (5PR, 10PR) adds a remanence limit. PX is defined by knee point voltage, excitation current and winding resistance. TPX, TPY, TPZ and TPS are transient classes for duties where the DC part of a fault matters. A CT PT analyzer evaluates all of these classes.
- 23Because the duties conflict. A metering core should saturate early to protect instruments, a protection core must stay linear far beyond rated current, and a transient core must handle the DC offset of a fault. So a CT carries several cores, each with its own terminals: for example 1S1-1S2 class 0.5, 2S1-2S2 class 5P20 and 3S1-3S2 class TPY.A CT PT analyzer tests one core at a time against its own class, with the other cores short-circuited.
- 24Yes, to a useful degree. The analyzer works backwards from its measurements. Rated secondary current comes from winding resistance, since a 5 A winding has much lower resistance than a 1 A winding. Rated primary current follows from the measured turns ratio, snapped to standard values.Accuracy class is found by first judging from saturation voltage whether the core is metering or protection, then testing the results against each class in turn and taking the first one the CT meets. It is a deduction, not a certificate, but for a CT with a corroded plate it turns a guess into knowledge.
- 25By how the core behaves at high current. A metering CT is precise across the normal load range and saturates early in a fault to protect the instruments. A protection CT may be less precise at load but must keep reproducing current far above rating so the relay sees the true fault.The two often look the same from outside. The CT PT analyzer's saturation measurement settles it.
- 26A CT is a current source. With the secondary closed through its burden, secondary current opposes the primary and the core flux stays low. Open the secondary while primary current flows and nothing opposes it: the core saturates deeply and very high voltages appear across the open terminals, high enough to kill and to destroy the insulation.That is why CT secondaries are shorted before any work on the circuit, and why no test lead should be disconnected while a test is running.
- 27Yes. For analysis, ratio and polarity tests, the primary must be disconnected from the line, because an unearthed primary connection injects noise into a measurement that works with small signals. For burden and winding resistance tests, the secondary must be disconnected from its loop.In a burden test, leaving the winding connected measures the loop and the winding together. With no degaussing step in a burden test, the CT winding is driven into saturation and the number is wrong.Disconnect the CT primary from the line and earth one side, so system noise stays out of the measurement.
- 28On a multi-core CT the cores are magnetically coupled through the shared primary, and an open core distorts the measurement of the core under test. Short-circuit the secondaries not under test whenever their rated primary and secondary currents are the same. For example, when testing the 0.5 metering core of a CT that also has 10P and TPY cores, short the 10P and TPY windings.Shorting a CT secondary is safe; leaving one open is not, so it is a good habit for safety as well as accuracy.Testing core 1S1-1S2 (class 0.5) on a 2000/1 A CT: cores 2S1-2S2 (5P20) and 3S1-3S2 (TPY) are shorted.
- 29The analyzer injects voltage into the secondary and compares the phase of primary and secondary voltages: less than 90° apart is correct polarity, more than 90° is reversed.A reversed CT in a differential scheme creates a false difference current and trips a healthy transformer. In a metering circuit it subtracts a phase instead of adding it. In a directional scheme it sends the relay the wrong way. It is the cheapest test to run and the most expensive to skip.
- 30Because copper resistance changes with temperature. The same winding measured on a cold morning and in summer heat gives different readings and, against a fixed limit, possibly different verdicts.So the analyzer records ambient temperature with the resistance and reports both the value at test temperature and the value corrected to a reference temperature, usually 75 °C, matching how the nameplate value is stated. The corrected value is compared with the limit.Winding resistance test: the measurement leads connect behind the power leads, so contact resistance does not affect the result.
- 31It compares every measured result with the limits of the standard and accuracy class you selected. For a metering class that means FS and the ratio and phase errors at each specified percentage of rated current. For a protection class it means ALF, the errors at rated current, and remanence for R classes.Every item must pass for the CT to pass; one failed item fails the CT. Because many results depend on burden, the evaluation can run at rated burden, actual burden or both, and a CT can pass one and fail the other.
- 32The instrument generates the report itself. It carries the test settings, transformer data, every measured value, the excitation curve, the pass or fail verdict, and the operator, company and location entered once in setup. It comes out in Word format, on the instrument or later on a PC, and several test records can be combined in one document.The real gain is no transcription: the numbers in the report are the numbers the instrument measured, not numbers typed into a spreadsheet at the end of a long day on site.
- 33The KPM CTA C+ runs on single-phase AC from 198 V to 264 V at 47 to 63 Hz. It works from -20 °C to 50 °C at up to 90% relative humidity, non-condensing, and should not be used in heavy damp.It must be earthed with its grounding cable for any test outside a laboratory, and one terminal of the CT primary should be confirmed earthed. It weighs 14 kg, so one person can carry it to the test position.
- 34For work in a high-voltage substation, yes: the operator should hold a high-voltage electrical test certificate, as the manual states.Beyond that, an analyzer automates the measurement, not the judgement. It will not stop you testing the wrong core, forgetting to short the others, or accepting a verdict against a standard that does not apply to the CT in front of you. The engineering stays with the engineer.
- 35Always at commissioning, and after that at the interval your maintenance standard or the asset's criticality sets; practice varies widely and there is no single universal figure.Two triggers matter more than any interval. Test after a CT has carried a heavy through-fault, because remanence and thermal stress change its behaviour. And test when a metering discrepancy appears, because a CT drifting out of class is one cause nobody checks until someone suggests it.
- 36IEC 61869 is the current standard series for instrument transformers, with IEC 61869-2 covering current transformers. It replaced the older IEC 60044 series (60044-1 for CTs, -2 for VTs, -6 for transient protection CTs). In North America the parallel standard is IEEE C57.13.The older numbering is still written into many utility specifications, nameplates and procedures, so both names will be around for years. The KPM CT PT Analyzer complies with IEC 61869 and can also evaluate results to IEC 60044 and IEEE C57.13 where a specification calls for them.
- 37Yes. Several NABL-accredited laboratories in India already list CT and PT analyzers, using the secondary injection method, in their scopes. NABL does not approve instruments; it accredits the laboratory. The lab needs a traceable calibration certificate for its analyzer, a validated method (compared against primary injection with a standard CT), and an uncertainty budget.With the KPM CTA C+'s ±0.05% ratio and ±2 minute phase accuracy, a lab can typically support a CMC of about 0.06% and 2.5 minutes. That suits protection CTs and metering CTs down to class 0.2 and 0.2S. Class 0.1 CTs still need primary injection against a standard CT.
- 38Function by function, against reference standards several times more accurate. Voltage and current measurement are checked with a precision multimeter and shunt, and winding resistance with standard resistors.Ratio and phase are checked by letting the analyzer test a standard CT whose errors have been certified by primary injection, at several ratios, both 1 A and 5 A, and at known burdens, then comparing results. The certificate should list every test point with the reference value, the reading, the error and the lab's uncertainty.
- 39Once a year is the usual expectation for test equipment in utility service, and tenders often ask for a valid calibration certificate at the time of supply. Every KPM CT PT Analyzer ships with an inspection report and a pass certificate.Between calibrations, re-testing the same stable CT every few months and plotting the results shows the analyzer is holding its accuracy, which NABL assessors like to see.
- 40Seven things, roughly in this order. The knee point voltage it can reach, which decides which CTs you can test. Measurement accuracy on voltage, current, ratio and phase. Which standards its evaluation supports, including IEC 61869. Whether it measures burden on the real secondary loop and gives errors at rated and actual burden.Whether it tests PTs as well as CTs. Whether it can deduce a missing nameplate, which matters more on old plant than it sounds. And what the report looks like, because that is what your customer receives.
- 4141. What is the price of a CT PT analyzer in India?The price depends on the configuration: whether you need PT testing, the optional 200 A current booster, transient (TP class) evaluation and accessories. That is why KPM quotes after a short technical discussion instead of publishing one list price.Tell us what you test (CT classes, voltage levels, site or lab) and we will send a quotation for the KPM CTA C+ that covers what you need and nothing you don't. Call 0124 4001088 or email sales@kpmtek.com.
- 42KPM Engineering Solutions in Gurugram, Haryana, supplies and supports the KPM CTA C+ CT PT analyzer across India. Our customers include testing and commissioning companies, utilities, EPC contractors, CT manufacturers and industrial plants.Buying from KPM means application support from engineers who test CTs themselves, before and after the sale. See the KPM CT PT Analyzer or call 0124 4001088.
- 43Yes. Start with a technical discussion of what you test, then see the KPM CTA C+ in a demonstration at your site, in an online video demonstration, or at an exhibition where we are exhibitingBring a CT you know well. Seeing the analyzer test a familiar CT tells you more than any brochure. To arrange a demo, call 0124 4001088 or email sales@kpmtek.com.
- 44
- 45
- 46Us, whether or not you have bought anything from KPM. Send the saved test record to sales@kpmtek.com with the transformer details, and one of our engineers will go through it with you.Most puzzling results come down to burden, remanence or the wrong standard being selected, and all three show up in the saved data. Answering these questions is how we learn what engineers actually struggle with.
- 47Yes. Repairs are carried out at the KPM service centre, and we arrange calibration with a traceable certificate. Contact us with the serial number and the issue, and we will confirm the turnaround before any work starts.Call first: many reported faults turn out to be a connection, a setting or a site supply problem that we can solve over the phone the same day.
- 48Every KPM CT PT Analyzer is warranted against defects in materials and workmanship for twelve months from dispatch. Within that period we repair or replace any unit that fails in normal service at no charge.Call us before opening the instrument, because opening the case voids the warranty. The warranty covers failure, not damage: physical damage, water ingress, repair or modification by others, consumables, and connecting high voltage or high current directly to the analyzer are excluded. Application support continues for as long as you own the instrument.SEO titleCT PT Analyzer FAQ: CT Testing, Knee Point, NABL | KPMMeta description48 answers on CT and PT testing with a CT PT analyser: knee point, excitation curve, ratio error, 5P20, IEC 61869 and NABL calibration. KPM, Gurugram.URL slug/what-is-a-ct-pt-analyzerPage heading (H1)CT PT Analyzer: Frequently Asked QuestionsConfirm before publishing: questions 12 and 26 (engineer sign-off), 37 (NABL CMC figure), 43 (demo options), 45 (hours and response time), 47 (repair and calibration) and 48 (12-month warranty).