KPM VIT100 Vacuum Interrupter Test : FAQ
- 01The KPM VIT100 checks the vacuum integrity of vacuum interrupters (vacuum bottles), either on their own or fitted inside a vacuum circuit breaker. It applies up to 60 kV DC across the open contacts, measures the leakage current in real time, and gives a pass or fail result. A healthy bottle holds the voltage with very little current; a bottle that has lost its vacuum breaks down or leaks heavily.
- 02The touchscreen in the centre runs the tester. Top left is the earth terminal; below it is the alarm (high-voltage warning lamp). Top right is the leakage current input terminal. Along the bottom are the AC 220 V power inlet, an RS232 port and the ON/OFF switch. The high-voltage output is on the top of the case.Picture: KPM VIT100 front panel
- 03
- 04After switch-on the DC HIPOT TEST main menu shows six quick-test voltage buttons, plus Settings and History, with the date and time at the bottom. Tap a voltage to open the test window for that voltage. Settings holds all set-up options; History opens the saved test records.Picture: Main menu: six quick-test voltages, Settings and History
- 05
- 06
- 07
- 08The tester produces up to 60 kV DC. Connect the ground cable from the earth terminal on the panel to a reliable earth before you enable the high-voltage output, and leave it connected until the circuit has been discharged. The earth protects the operator and gives the leakage current a safe return path.
- 09Isolate the breaker from the system and earth it as your permit-to-work requires; open the breaker. Earth the tester first. Use only the supplied cables. Keep everyone outside a barrier while the output is on, which also protects against X-rays that vacuum interrupters can emit at high voltage. Never exceed the interrupter manufacturer's test voltage. Only operators qualified for high voltage testing under local rules should run the test.
- 10In very dry conditions your body can pick up static charge when you stand close to a DC high-voltage circuit, and you may feel a light shock when you touch earth. Wear anti-static shoes or hold an earth ground cable when testing in extremely dry environments, and keep a safe distance from the high-voltage circuit.
- 11First connect the earth terminal to earth ground. Then connect the high-voltage cable from the HV output to one terminal of the vacuum interrupter, and connect the other terminal to the leakage current input with the sampling cable. The breaker must be open, so the test is across the open contact gap. In a breaker, test each pole in turn.Picture: Test connection for a vacuum interrupter
- 12
- 13
- 14
- 15
- 16Settings, then Test voltage. Each button covers a band, shown next to it: 5–10, 11–20, 21–30, 31–40, 41–50 and 51–60 kV. Tap a value, type the new voltage on the keypad (1 kV steps, within the band) and press OK. The values are stored and appear on the main menu every time you switch on. Save the levels for the breaker classes you maintain most.Picture: Six quick-test voltages and their ranges
- 17
- 18
- 19Settings, then Test current. Enter any value from 1 to 300 µA (the allowed range is shown in red beside the box) and press OK. If the leakage current goes above this limit during a test, the tester stops and the result is a failure. Use the limit given by the interrupter manufacturer or your maintenance standard.Picture: Leakage current limit setting
- 20
- 21
- 22
- 23Tap the voltage you want on the main menu. The test window shows Output voltage, Leakage current, Target voltage and Test time (set time / elapsed time). Check that voltage and current read zero, then tap Start. The voltage rises slowly to the target, the timer runs while it is held, and the output then falls back to zero. Stop ends the test at any time; Return goes back to the main menu.Picture: Test window, ready to start
- 24
- 25
- 26
- 27
- 28The tester protects itself and stops the test if there is a breakdown in the test circuit, if the leakage current exceeds your limit, or if it detects an internal fault. The screen asks you to restart the instrument: switch it off and on again. Discharge the test circuit with the discharge stick before touching any connection.Picture: Protection message
- 29Not always. A flashover across the outside of the interrupter housing, caused by dust or moisture, looks like a failure too. Clean and dry the outer surface, check that the contacts are fully open and the connections are secure, and test again. If it fails again under good conditions, treat the bottle as having lost its vacuum and replace it as the breaker manufacturer advises.
- 30Yes. The KPM VIT100 discharges the high-voltage circuit automatically when the test ends, but this takes time and charge can remain. Even when the display reads 0 kV, and even after switching the tester off, always discharge the circuit with the earthed discharge stick before removing any connection.
- 31
- 32
- 33
- 34
- 35
- 36Output up to 60 kV DC, maximum current 0.5 mA. Voltage measurement error under 3% + 0.1 kV, resolution 0.1 kV. Leakage current 0–300 µA, error under 3% + 1 µA. Test time 1–60 s. Six quick-test voltages, 1 kV setting resolution. Leakage limit 1–300 µA. 100 stored records. Power AC 220 V ±10%, 45–65 Hz, 100 W or less. 0–50 °C, up to 85% RH. 405 × 318 × 215 mm, 9 kg.
- 37
- 38
- 39
- 40